Answer ALW/WALW – Alarm – PS161-6 can run up to 8 devices. Any 24VDC filtered and regulated power supply with .25 amps per device can be used. DE – Delayed egress – PS161-6. Each power supply can run up to 4 devices. No other power supply can be used due to the UL listing. E – Electric lock/unlock of the trim – RPSML2 or RPSMLR2BB can run up to 2 devices. The PS161-6 can run up to 8 devices. Any 24VDC filtered and regulated power supply with .3 amps per device can be used. ELR – Electric latch retraction – ELR151, ELR152, ELR153, or ELR154 depending on the number of devices. No other power supply can be used. MLR – Motorized latch retraction – RPSMLR2 or RPSMLR2BB. The BB is for battery backup. Each power supply can run 2 devices. Any 24VDC filtered and regulated power supply with 1.5 amps per device can be used. |
|
Additional information Here are the links to the instructions. ELR150 https://dhwsupport.dormakaba.com/hc/article_attachments/4415914437787 https://dhwsupport.dormakaba.com/hc/article_attachments/4415898074139 https://dhwsupport.dormakaba.com/hc/article_attachments/4415968273563
RPSMLR2 https://dhwsupport.dormakaba.com/hc/article_attachments/25772775110043
PS161-6 https://dhwsupport.dormakaba.com/hc/article_attachments/11123728882459 |
|